Selecting the Appropriate Fuse Rating When Installing the 120A SI ACR

When installing Blue Sea Systems 120A SI ACR, PN 7610, use this chart to select the appropriate wire size and fuse rating.

Wire sizing chart (AWG)

Charging Amps

Minimum Wire Size*

Fuse Amps

60

#6

80

80

#4

110

100

#2

150

120

#1

175

Wire sizing chart (Metric)

Charging Amps

Minimum Wire Size*

Fuse Amps

50

10 mm²

75/80

70

16 mm²

80/90

90

25 mm²

125/130

110

35 mm²

150

120

50 mm²

150/175


Fuses installed between ACR terminals A and B, and each battery positive are to prevent a hazard if there is damage to the wires from the batteries to the ACR. Therefore, the fuses should be placed as close as possible to the batteries so that most of the wire is protected.

Since these fuses connect directly to batteries, choose fuse types that have sufficient AIC for your battery bank. ANL fuses and Terminal Fuses are ideal for this application.